APPENDIX C
MX480 Router Environmental
Specifications
•
MX480 Router Environmental Specifications on page 283
MX480 Router Environmental Specifications
Table 28 on page 283 specifies the environmental specifications required for normal router
operation. In addition, the site should be as dust-free as possible.
Table 28: Router Environmental Specifications
ValueDescription
No performance degradation to 10,000 ft (3048 m)Altitude
Normal operation ensured in relative humidity range of 5% to 90%,
noncondensing
Relative humidity
Normal operation ensured in temperature range of 32°F (0°C) to
104°F (40°C)
Nonoperating storage temperature in shipping container:
–40°F (–40°C) to 158°F (70°C)
Temperature
Designed to meet Telcordia Technologies Zone 4 earthquake
requirements
Seismic
AC power: 11,322 BTU/hour (3,318 W)
DC power: 9,632 BTU/hour (2,823 W)
NOTE: These specifications are estimates and subject to change.
Maximum thermal output
NOTE: Install therouter only in restricted areas, such as dedicatedequipment
rooms and equipment closets, in accordance with Articles 110-16, 110-17, and
110-18 of the National Electrical Code, ANSI/NFPA 70.
283Copyright © 2013, Juniper Networks, Inc.