Juniper Networks EX2200 Bedienungsanleitung Seite 64

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 176
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 63
If you are mounting an EX2200 switch in a rack or cabinet with other equipment, or if
you are placing it on the desktop or floor near other equipment, ensure that the exhaust
from other equipment does not blow into the intake vents of the chassis.
Leave at least 24 in. (61 cm) in front of the switch and 6 in. (15.2 cm) behind the switch.
For service personnel to remove and install hardware components, you must leave
adequate space at the front and back of the switch. NEBS GR-63 recommends that
you allow at least 30 in. (76.2 cm) in front of the rack or cabinet and 24 in. (61 cm)
behind the rack or cabinet.
Related
Documentation
Rack Requirements for EX2200 Switches on page 39
Cabinet Requirements for EX2200 Switches on page 40
General Site Guidelines for EX Series Switches on page 35
Rack-Mounting and Cabinet-Mounting Warnings for EX Series Switches on page 129
Cooling System and Airflow in an EX2200 Switch on page 15
Copyright © 2010, Juniper Networks, Inc.44
Complete Hardware Guide for EX2200 Ethernet Switches
Seitenansicht 63
1 2 ... 59 60 61 62 63 64 65 66 67 68 69 ... 175 176

Kommentare zu diesen Handbüchern

Keine Kommentare